- Back |
- Home page
- / About Us
- / Haiwell News
- / Haiwell PLC-Specification of C/T/H/N series
Performance Specification
Item | Specification | Declare | |
Execution speed | 0.05μs/basic instruction | ||
Program language | LD(ladder) + FBD(function block) + IL( instruction list) | Accord with IEC 61131-3 | |
Program capacity | 48K | ||
Storage Method | Flash ROM permanent storage, dispense with backup battery | ||
X | External input | X0~X1023 | Support edge catch and signal filtering set |
Y | External output | Y0~Y1023 | Power-off preserve output can be configured |
M | Auxiliary relay | M0~ M12287 | Power-off preserve area can be set freedom |
(default power-off preserve) M1536~M2047 | |||
T | Timer (output coil) | T0~T1023 | Power-off preserve area can be set freedom, time base: 10ms, 100ms, 1s be set freedom,T252~T255 1ms |
(default power-off preserve) T96~T127 | |||
C | Counter (output coil) | C0~C255 | Power-off preserve area can be set freedom |
(default power-off preserve) C64~C127 | |||
S | Step state bits | S0~S2047 | Power-off preserve area can be set Freedom |
(default power-off preserve) S156~S255 | |||
SM | System state bits | SM0~SM215 | |
LM | Local relay | LM~LM31 | |
AI | Analog input register | AI0~AI255 | Support quantities convert, sample times and zero point correct |
AQ | Analog output register | AQ0~AQ255 | Support quantities convert, power-off preserve output can be configured |
V | Internal data register | V0~V14847 | power-off preserve area can be set freedom |
(default power-off preserve) V1000~V2047 | |||
TV | Timer (Current value register) | TV0~TV1023 | Power-off preserve area can be set freedom, time base: 10ms, 100ms, 1s can be set freedom, T252~T255 1ms |
(default power-off preserve) TV96~TV127 | |||
CV | Counter (Current value register) | CV0~CV255 | Power-off preserve area can be set freedom, CV48~CV79 are 32 bits, Other are 16 bits |
(default power-off preserve) CV64~CV127 | |||
SV | System register | SV0~SV900 | |
Lv | Local Register | Lv0~Lv31 | |
P | Indexed addressing point | P0~P9, use for indirect addressing | |
I | Interrupt | I1-I52 | |
LBL | Lable | 255, use for program skip | |
Communication port | MPU built-in 2 communication port (RS232/RS485), Max 5 communication port (RS232/RS485) Extension | Can be used for programing or networking (master/slave) | |
Communication protocol | Modbus RTU/ASCII protocol, freedom communication protocol, Haiwellbus speed communication protocol, Baud rate 1200~115200bps | ||
PLC network capacity | PLC communication address can be set external set, Max 254, support 1: N, N: 1, N: N network | ||
Real time clock (RTC) | Display: year /month /day /hour /minute /second /week | Built-in battery | |
Float point arithmetic instruction | Support within 32 bits float point arithmetic, integer/float point convert arithmetic | ||
Password protect | Support 3 level password protection: Program file password Program block password PLC hardware password and upload prohibited function |
Power specification
Item | AC Supply | DC Supply | |
Input power supply | AC100~240V | DC24V -15%~+20% | |
Power supply frequency | 50~60Hz | --- | |
Instant surge | MAX 20A 1.5ms @220VAC | MAX 20A 1.5ms @24VDC | |
Power output | MAX 25VA | --- | |
Permit Power supply lost | 20ms within @220VAC | 10ms within | |
Fuse capacity | 2A,250V | 2A,250V | |
Action (working) specification | When input power voltage rise to 95~100VAC, PLC will be run, when input power voltage drop down to 70VAC, PLC will be stopped. | --- | |
Output power supply | 5VDC for CPU | 5V,-2%~+2%,1.2A(maximum) | 5V,-2%~+2%,1.2A(maximum) |
24VDC power supply for output and Extension modules | 24V,-15%~+15%,500 mA(maximum) | 24V,-15%~+15%,500mA (maximum) | |
24VDC power supply for input and external device | 24V,-15%~+15%,200mA(maximum) | Direct use the 24VDC input power supply | |
Isolation model | Transformer/photo electricity isolation,1500VAC/1 minute | No electrical isolation | |
Protect the power supply | DC24V output over the limit of the current | DC power input polar against, over voltage |
Product environment specification
Item | Environment Specification |
Temperature/Humidity | Working temperature: 0 ~ + 55 ℃ storage temperature: - 25 ~ + 70 ℃ and humidity: 5 ~ 95% RH, no condensation |
Anti vibration | 10~57Hz range 0.075mm,57Hz~150Hz acceleration 1G,X, Y, Z three axis 10 times each direction |
Anti shock | 15G,contiune 11ms,X, Y, Z three axis 6 times each direction |
Anti jamming | AC EFT: ± 2500V, surge: ± 2500V, DC EFT: ±2500V, surge: ±1000V |
Over voltage capability | Between AC terminal and PE terminal 1500VAC,1min,Between DC terminal and PE terminal 500VAC,1min |
Insulation impedance | Between AC terminal and PE terminal@500VDC,>=5MΩ(Between all input/output terminal and PE terminal@500VDC) |
Earth | The third grounding(Cannot connect to the strong power system’s earth) |
Operation environment | Operated where no dust, moisture, corrosion, electrical shock and physical shock ,etc. |
APP
© 2005 Xiamen Haiwell Technology Co., Ltd. All Rights Reserved.
4F, No. 336-2, Anbian Nan Road, Torch High-tech Zone (Xiang 'an) Industrial Zone, Xiang 'an District, Xiamen, Fujian, China 361101